RLW &RCS-3N type medium-voltage pole mounted vacuum load break switch is a 3 phase full new design technology switch. Its used on overhead distribution lines as well as distribution substation applications for voltage classes 11kV up to 38kV. and its rated current can reach up to 1250A.
Summary
1.1 General
RLW &RCS-3N type medium-voltage pole mounted vacuum load break switch is a 3 phase full new design technology switch.
Its used on overhead distribution lines as well as distribution substation
applications for voltage classes 11kV up to 38kV. and its rated current can
reach up to 1250A. System solution for switching and sectionalizing line as well
as automation and control systems,
e.g. in:
■ Power plants
■ Switching
substations
■ Companies in all industrial sectors
■ Water treatment plants
■
Office and administrative buildings
■ Airports and logistic centres
■
Oil/Gas plants
1.2 Standards and specifications
1.2.1 Switchgear manufacture
The
switchgear complies with the following specifications in accordance with
relevant IEC
publications:
• IEC62271-100/ GB1984-2003 or ANSI/IEEE
C37.66
1.3 Operating conditions
1.3.1 Normal operating conditions
Design to relevant standard, with the following limit values:
• Ambient
temperature:
–Maximum +40℃, –Maximum 24 hour average +35℃
–Minimum
(according to “minus 5 indoor class”) –40℃
• Humidity:
–Monthly
average humidity 95%; Daily average humidity 90% .
• Maximum site
altitude: ≤ 3000 M above sea level.
1.3.2 Special operating conditions
Special
operating conditions are to be agreed on by the manufacturer and user.
The
manufacturer must be consulted in advance about each special operating
condition:
• Site altitude over 1000 m:
–Allow for the
reduction in the dielectric strength of the air.
• Increased ambient
temperature:
–Current carrying capacity is reduced.
–Provide
additional ventilation for heat dissipation.
• Climate:
–Avoid
the risk of corrosion or other damage in areas:
• with high humidity
and/or with major rapid temperature fluctuations.
– Implement
preventive measures (e.g. electric heaters) to preclude condensation phenomena.
2. Main new advantages of RLW (RCS-3N)
2.1 The VLBS tank feature:
The Vacuum load break switch tanks are manufactured from 304#grade stainless steel and standard tank are powder coated a light grey colour. Whole load break switch IP65 protection class, equipped with a auxiliary plug to connect with load break switch controller by control cable, Diameter Max22mm, up to 6 M length(8M for special).It can performance serve more than 20 years long term under heavy duty circumstance.
2.2 The vacuum embedded pole feature:
The load break switch’s vacuum interrupter insert in an epoxy resin solid pole, and external coated with a high reliable, stable material: Fluorocarbon silicone rubber (γ-trifluoro propyl methyl polysiloxane) With excellent electric insulation, weather resistance, ozone, biological inertia, can be stand under the long-term use in -55 ~ +200 ℃.
2.3 Creepage Distances of RLW (RCS-3N)
Description | 15kV BIL95kV | 15kV BIL110kV | 27kV BIL125/150kV | 38kV BIL150/170kV |
T to T* | 480mm | More than 968mm | ||
T to G/E* | 480mm | More than 960mm |
T to T* -----Terminal to terminal creepage
T to G/E* -----Terminal to ground/earth creepage
3. Optional for difference functions of primacy design
3.1 Optional for Difference configurations of primacy design (Interruptering pole)
Basic VI pole,BIL170kV VI pole with CT,BIL170kV
Note:RLW (RCS-3N) is ready design for primacy optional :Standard type and special type with CT for relay protection and current measuring purpose.
3.2 Optional for disconnector switch ( Special requirement using combination switch)
With manually and motorized double function.
Note:
This disconnector switch is ready design for RLW (RCS-3N) primacy optional.This
is special design for combination switch application.
3.3 Simple relay protection device (mounted inside of mechanism tank)
Type P-1 protector is a composite protection device for the power system while
inrush current and short circuit, to avoid closing inrush and during the
operation of the surge protection and short circuit quick break.
Main technical parameters:
1, Rated current: AC5A; Action current error: ± 5%; P-1 controller
2, Delay time: the time limit set, the inverse time adjustable range 20ms ~
5120ms;
3, Optional for remote Controller: Distance100 m or 1000 m.
3.4 Expanding for sectionalizer switch protection device
3.4.1Type P-2 protector have the same relay protection functions as P-1.
3.4.2 The additional functions:
3.4.3 With zero-sequence protection function, be able to judge the failure of
sensitive current earthing fault.
3.4.4 Cycle record a variety of line fault, save the fault time current,
non-volatile, and a maximum storage of 64, you can query the local liquid
crystal display, but also by the background software queries. P-2
Controller
3.4.5 All the way to the wireless network interface cards (optional), at a
distance within 200 meters of the machine can communicate with the computer's
wireless network;
3.4.6 RS232 communication port, connection with the GSM, GPRS / CDMA
communication module to build the distribution network automation system;
3.4.7 Communication protocols to support the Statute of the IEC870-5-101.
Note:This is expanding products for LBS with CT protection.More information PLS consult with Roclwill’s Engineer and Sectionalizer switch technical manual.
3.5 Sheet for define of difference function switch
Item |
Type and code |
Description of function |
1 | RLW-12/630-20 | Basic switch , rating voltage 12kV and rated current 630Aand short circuit withstand current 20kA |
2 |
RLW12G/63020 |
Basic switch with disconnector switch, rating voltage 12kV and rated current 630A and short circuit withstand current20kA |
3 | RLW-12G/630P20 | Basic switch with disconnector switch, rating voltage 12kV and rated current 630A and short circuit withstand current 20kA. And with Current transformer 600/5A for relay protection. |
4 | RCS-3N-12/630-20 | Same function as item 1 |
5 | RCS-3N-12G/630-20 | Same function as item 2 |
6 | RCS-3N-12G/600P20 | Same function as item 3 |
Note: Special order or requirement can consult with Rockwill’s Engineer.
4. Overview of vacuum load break switch mechanism
4.1 The feature of mechanism frontal side
4.1.1 The mechanism for RLW(RCS-3N) is mounted inside a stainless steel tank.
With IP65 class protection.
4.1.2 The tank is provided with visible ON/OFF indicator and a M12 grounding
bolt.
4.1.3 The tank is pre-provided with cable connector for connecting to controller
box or junction box..
4.1.4 RLW and (RCS-3N) type load break switch is provided with optional for
Manual or Motorize charging type mechanism. Mechanical life 10,000 times design,
free maintenance for 2000 times.
Operating voltage optional:
-24 Vdc,
-48 Vdc,
-110 Vdc and 110Vac,
-220 Vdc and 220Vac.
Note:For operating voltage requirement should indicated before order.
More information Pls consult with Rockwill’s Engineer.
5. Overview of junction box and controller for LBS
5.1 The feature of simple function junction box(Type J-1 junction box)
The type J-1 box is made by stainless steel with IP54 class protection.The J-1
junction box is only for connection with control centre.Its terminals and wires
in side without switches Or relay components. Insulation level P fr
=3000V.Terminal rating current = 10A.
Note:1. This junction is basic using for LBS without CT and DS terminals. 2. Its
only for connection with centre controlling wiring.
5.2 The feature of simple control box(Type C-2 controller)
The Type C-1 controller box is made by stainless steel with IP54 class protection
design. With controlling and remote and local transform function. Can be
setting between HV switch(RLW or RCS-3N) and Control centre for connection and
controlling using.The wiring components of C-1 type box is including pushbutton,
rotate switch , MCBs, and some signal lights, etc.
Note:
1. Per IEC62271-200 Standard.
2. This controller can be mounted with simple relay protector.
3. Heater and humidity controller is optional.
4. For this controller using, the LBS can be equipped with CTs.
5.3 The feature of expanding intelligence controller.(P-2 Controller)
5.3.1Type P-2 protector have the same relay protection functions as P-1.
5.3.2 The additional functions:
5.3.3 With zero-sequence protection function, be able to judge the failure of
sensitive current earthing fault.
5.3.4 Cycle record a variety of line fault, save the fault time current,
non-volatile, and a maximum storage of 64, you can query the local liquid
crystal display, but also by the background software queries.
5.3.5 All the way to the wireless network interface cards (optional), at a
distance within 200 meters of the machine can communicate with the computer's
wireless network;
5.3.6 RS232 communication port, connection with the GSM, GPRS / CDMA
communication module to build the distribution network automation system;
5.3.7 Communication protocols to support the Statute of the IEC870-5-101.
Note:
This is expanding products for LBS with CT protection. More information PLS
consult with Roclwill’s Engineer and Sectionalizer switch technical manual.
6.1 Basic of switch specification
No. | Item | Unit | Data | ||||
1 | Rated voltage | KV | 12 | 15 | 27 | 38 | |
2 | Rated current at Max | A | 1250 | 1250 | 1250 | 800 | |
3 | Rated frequency | Hz | 50/60 | ||||
4 | Power frequency 1 min | Dry | KV | 34 | 38 | 50 | 70 |
Wet | KV | 45 | 50 | 65 | 80 | ||
5 | Lightning impulse withstand voltage(peak value)alternate | A | 75 | 95/110 | 125/150 | 150/170 | |
6 | Rated short circuit breaking current at 50times | KA | 9000 | 9000 | 9000 | 4500 | |
7 | Rated short circuit withstand current | S | 12.5 | 8 | |||
8 | Short time duration time | KA | 3S | ||||
9 | Rating making current | KA | 40 | 20 | |||
10 | Rated peak value withstand current | KA | 40 | 20 | |||
11 | Rated operating circulate | O-0.3S-CO-15S-CO | |||||
12 | Mechanical life(Design) | times | 10000 | ||||
13 | Mechanical life(free maintenance) | 2000 | |||||
14 | electrical life(free maintenance) | 2000 |
Note:
Electrical endurance is base on the VI design.
Higher requirement for breaking and making can consult with Rockwill’s engineer.
6.2 Special requirement for increasing electrical characters of switch
No. | Item | Unit | Data |
1 | Short circuit breaking capacity | kA | Up to 25kA |
2 | Rating short time making current | kA | Up to 63kA |
3 | Electrical life endurance | times | Up to 30000 times design under normal load switching |
4 | Mechanical life endurance | times | Up to 10,000 times design under mounted with mechanism of magnetic actuator(RCS-3 type) |
Note:
More information needed Pls check with RCS-3 switch
7.1 Pole mounted LBS-Basic switch 12kV
12kV basic switch. –without CTs, and disconnector switch
Combination switches with disconnector switch
Optional for surge arresters.
Optional for crrent transformers.
Note: More information needed Pls consult with Rockwill.
7.2Pole mounted LBS-Basic switch 15/27kV
15/27kV basic switch- without CTs and disconnector switch. With phase distance 360mm.Expanding to 38kV needed, increasing the phase distance to 435mm.
Combination switches with disconnector switch
Optional for surge arresters.
Optional for crrent transformers.
Note:More information needed Pls consult with Rockwill.